7HD High Density Portland Based Fireproofing
|
|
Descriptions Southwest Fireproofing Type 7HDTM is a spray-applied, factory blended high density cementitious fireproofing for the more demanding service conditions. The higher density of Type 7HDTM produces a harder and stronger protection than normal or medium density products. Specific Uses Type 7HDTM is formulated to provide excellent hardness and durability for use on building structures where accidental physical damage is a primary concern. Benefits Type 7HDTM sets and cures to form a hard and durable monolithic barrier that remains in place under harsh conditions. Type 7HDTM is cost effective because of excellent workability, spraying and adhesion characteristics. Applications Type 7HDTM is used in high density service conditions as shown in the Selection Chart.
|
TYPE 7HDTM CEMENTITIOUS FIREPROOFING IS SPRAY-APPLIED TO STRUCTURAL COMPONENTS OF BUILDINGS FOR FIRE RESISTANCE. UNDERWRITERS LABORATORIES FIRE TEST RESULTS HAVE QUALIFIED IT FOR USE IN OVER 100 DESIGNS. UL DESIGN PAGE
TYPE 7HDTM CEMENTITIOUS FIREPROOFING IS DERIVED FROM THE BENEFICIAL COMBINATION OF PORTLAND CEMENT AND VERMICULITE. IT IS NON-COMBUSTIBLE AND UNDER FIRE, IT RELEASES WATER OF CRYSTALLIZATION WHICH TURNS TO STEAM AND RETARDS HEAT TRANSFER.
|
Physical Characteristics of Type 7HDTM |
|
|
Property and Test Method |
Value / Result* |
|
Density, ASTM E-605 |
40 pcf (636 kg/m3) nominal |
| Combustibility, ASTM E-136 | Passed, non-combustible |
|
Compressive Strength, ASTM E-761 |
350 lb/in2 (2411 kPa) |
|
Cohesion/Adhesion, ASTM E-736 |
›6,000 lb/ft2 (›287 kPa) |
|
Effect of Impact, ASTM E-760 |
Passed, no cracking or delamination |
|
Effect of Deflection, ASTM E-759 |
Passed, no spalling or delamination |
|
Corrosion of Steel, ASTM E-937 |
Passed, no contribution to corrosion |
|
Erosion by Air, ASTM E-859 |
Passed, 0.000 g/ft2 (0.00 g/m2) |
|
Surface Burning, ASTM E-84 |
Flame Spread 0, Smoke 10 |
|
Hardness, ASTM D2240 |
40, Shore D |
|
Fire Resistance, ASTM E-119 |
Passed, see UL DESIGNS |
|
Fungi Resistance, ASTM G-21 |
Passed, no growth with optional fungicide |
|
* Values are from laboratory tests under controlled conditions and not intended to replace industry standards for specification purposes. |
|